Control and Monitoring Modules for use with the Raychem NGC-40 System Installation Instructions

LÝSING

The Raychem NGC-40-BRIDGE module provides the interface between a panel’s internal CAN-based network and upstream devices. Multiple communications ports are supported, allowing serial and Ethernet connections to be used with external devices.

VERKLEIKAR ÞARF

  • Lítið flatskrúfjárn

VIÐBÓTAREFNI

  • Power supply 24 Vdc @150 mA per NGC-40-BRIDGE
  • Sérsmíðaðar CAN snúrur með RJ-45 tengingum

INNIHALD SETJA

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (1)

Atriði Magn Lýsing
A 1 NGC-40-BRIDGE module
B 2 CAN bus termination block PTM# 10392-043
C 2 RS-485 termination resistors 120 Ω – 1% – 1/4 watt
D 1 NGC-40-BRIDGE serial cable TTC# 10332-005

Sérstök notkunarskilyrði:

  • The overall equipment is evaluated to type of protection “ec”
  • For full connection details see these installation instructions
  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1
  • The equipment shall be installed an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC/EN 60079-0
  • Veita skal skammtímavörn sem er stillt á stigi sem er ekki yfir 140% af hámarksrúmmálitage value at the supply terminals to the equipment

VIÐVÖRUN:
Þessi íhlutur er raftæki sem verður að setja upp rétt til að tryggja rétta virkni og koma í veg fyrir rafstuð eða eld. Fyrir tæknilega aðstoð, hringið í Chemelex á 800-545-6258.

ALMENNT 

Framboð binditage 24 VDC ± 10%
Innri orkunotkun <3.6 W per NGC-40-BRIDGE
Rekstrarhitastig umhverfisins –40°C til 65°C (–40°F til 149°F)
Geymsluhitastig umhverfisins –55°C til 75°C (–67°F til 167°F)
Umhverfi PD2, CAT III
Hámark hæð 2,000 m (6,562 fet)
Raki 5 – 90% óþéttandi
Uppsetning Din Rail – 35 mm

RAFSEGLUSAMLÆGI

Losun EN 61000-6-3 Losunarstaðall fyrir íbúðarhúsnæði, atvinnuhúsnæði og léttan iðnað
Ónæmi EN 61000-6-2 ónæmisstaðall fyrir iðnaðarumhverfi

COMMUNICATIONS COM1, COM2

Tegund 2-víra RS-485
Kapall Eitt hlífðar brenglað par
Lengd 1,200 m (4,000 fet) hámark
Magn Allt að 255 tæki á hverja tengi
Gagnahraði 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K baud
Gagnabitar 7 eða 8
Jöfnuður Ekkert, jafnvel, skrýtið
Stöðva bita 0, 1, 2
Tx delay 0 – 5 sek.
Bókun Modbus RTU eða ASCII
Tengistöðvar Wago cage clamp skautanna

COMMUNICATIONS COM3

Tegund RS-232
Kapall Custom TTC# 10332-005
Lengd 15 m (50 fet) hámark
Gagnahraði 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K baud
Gagnabitar 7 eða 8
Jöfnuður Ekkert, jafnvel, skrýtið
Stöðva bita 0, 1, 2
Tx delay 0 – 5 sek.
Bókun Modbus RTU eða ASCII
Tengistöðvar RJ-11

GETUR NETHAFN

Tegund 2-víra einangrað CAN-undirstaða jafningjanet. Einangrað í 300 V.
Tenging Tvö 8-pinna RJ-45 tengi (bæði má nota fyrir inntaks- eða útgangstengingar)
Bókun Séreign NGC-40
Topology Daisy keðja
Lengd 10 m (33 fet) hámark
Magn Up to 80 CAN nodes per network segment
Heimilisfang Einstakt, verksmiðjuúthlutað

Ethernet

Tegund 10/100 BaseT Ethernet network
Lengd 100 m (328 fet)
Gagnaverð 10 or 100 MB/s
Bókun Modbus/TCP
Tengistöðvar Shielded 8-pin RJ-45 connector on front of module

PROGRAMMING AND SETTING

LED vísar
Viðvörunarskilyrði RESET, Configuration lost, CAN communications fail
Stillingarrofi SET/RUN slide switch on front of module

TENGSLUTGÖNGUR

Raflögn Búr clamp, 0.5 til 2.5 mm² (24 til 12 AWG)
CAN netkerfi og einingaafl Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.

HÚSNÆÐI

Stærð 45.1 mm (1.78 tommur) á breidd x 87 mm (3.43 tommur) á hæð x 106.4 mm (4.2 tommu) djúpt

Kerfishlutir

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (4)Raflagsstöðvar

Flugstöðvar Virka
1 COM 1 (485) + in
2 COM 1 (485) + out
3 COM 2 (485) + in
4 COM 2 (485) + out
5 COM 1 (485) – in
6 COM 1 (485) – out
7 COM 2 (485) – in
8 COM 2 (485) – out
9 – 12 Ekki notað

 Stöðuljós

Staða: Gefur til kynna stöðu of the mát
Slökkt Enginn kraftur
Grænn OK/Normal
Gulur (flashing) Configuration mode
Rauður (flashing) Internal fault
NETWORK: Indicates CAN network activity
Slökkt Enginn tengill fannst
Grænn Link OK, receive data packets
Gulur Transmit data packets
Rauður (flashing) Network error
COM: Gefur til kynna COM1 & 2 (RS-485) starfsemi
Slökkt Engin virkni
Grænn (flashing) Receipt of data packet
Gulur (flashing) Transmit of data packet

Communication Slide Switch

 RS-232 höfn

Staða: Gefur til kynna stöðu of RS-232 höfn
Topp LED
Slökkt Engin virkni
Grænn (flashing) Receipt of data packet
Neðri LED
Slökkt Engin virkni
Gulur (flashing) Transmit of data packet

E. Ethernet Port

Staða: Gefur til kynna stöðu of the LAN
Topp LED
Slökkt No LAN detected
Grænn ON, LAN detectedt
Neðri LED
Slökkt Engin LAN virkni
Gulur (flashing) LAN activity (data packet)

CAN Bus/Module Power

 Endurstilla hnappur

Mounting the NGC-40-BRIDGE

  • Each NGC-40-BRIDGE mounts on a DIN 35 rail.
  • MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip.
  • FJARLÆGING: Ýtið einingunni upp til að losa klemmuna og snúið henni síðan að ykkur.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (5)RS-485 Connection Diagrams – North American Installation Technique

COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (6)

COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (7)

RS-485 Connection Diagrams – European Installation Technique

COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar. Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (8)

COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.

Local RS-232 (COM 3) & EthernetRaychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (9)

Switch Setting RS-232
User Interface – Configuration Switch
A slide switch is provided on the front of the module to allow the user to set the bridge into a known state for configuration of the communication ports, as shown in the following table:

Skipta Staða
Bridge Module Settings SETJA Stillingar ham HLAUP Venjulegur rekstur ham
Modbus heimilisfang 1
Staðbundin RS-232
Bókun RTU Settings based on the user configuration parameters
Gagnahraði 9600 baud
Gagnabitar 8
Stöðva bita 2
Jöfnuður Enginn jöfnuður

RMM2 Connection – Optional
When using the field mounted RMM2 for RTD input, it must be connected to the COM 2 In as shown below.

 

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (11) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (12)

NGC-40 CAN Bus tengingar fyrir allt að 10 einingar

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (13)

NGC-40 CAN Bus tengingar fyrir allt að 20 einingar

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (14) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (15)

CAN Bus Termination Block
A termination block (included) is required at each end of the CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (16)

Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel*

  1. Gefðu viðeigandi spjaldshólf
    The NGC-40-BRIDGE must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.
    Note: The Raychem NGC-40-BRIDGE is designed for operation in ambient temperatures from –40°C to 65°C (–40°F to 149°F ). If the ambient temperature is outside this range, a space heater and/or cooling fan will be required in the panel.
  2. Determine locations for the NGC-40-BRIDGE assembly in the electrical panel.
    The NGC-40-BRIDGE should be located in the rear of the panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.
    * North American panel installation techniques

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (17)

NGC-40 CAN Bus tengingar fyrir allt að 40 einingar Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (18) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (19) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (20)

SAMÞYKKTIR

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (2)Hættulegir staðir
Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx ec IIC T4 Gc IP20 Ex ec IIC T4 Gc X –40°C ≤ Ta ≤ +65°C

Í samræmi við:
FM STD 3600 & 3611, UL STD 121201, 60079-0, 60079-7, 61010-1, 61010-2-201

Löggiltur til:
CSA STD C22.2# 213, 60079-0, 60079-7, 61010-1, 61010-2-201

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (3)(Rússland, Kasakstan, Hvíta-Rússland)
Fyrir önnur lönd, hafið samband við Chemelex fulltrúa á ykkar svæði.

  • IEC Ex Markings: IECEx ETL 17.0062X Ex ec IIC T4 Gc
  • ATEX Markings: ITS17ATEX402833X II 3 G Ex ec IIC T4 Gc

Norður Ameríku

Rómönsku Ameríku

Evrópa, Mið -Austurlönd, Afríka, Indland

Asíu Kyrrahaf

Algengar spurningar

What approvals does the NGC-40-BRIDGE module have?

The module conforms to FM STD 3600 & 3611, UL STD 121201, 60079-0, 60079-7, 61010-1, 61010-2-201 and is certified to CSA STD C22.2# 213, 60079-0, 60079-7, 61010-1, 61010-2-201. It also has IEC Ex and ATEX markings for specific regions.

How many communication ports are supported by the NGC-40-BRIDGE module?

The NGC-40-BRIDGE module supports multiple communication ports for both serial and Ethernet connections with external devices.

What is the purpose of the CAN bus termination block included in the kit?

The CAN bus termination block is used for terminating the CAN bus network to ensure proper signal integrity and communication within the system.

Is the NGC-40-BRIDGE module suitable for use in hazardous locations?

Yes, the module is approved for use in hazardous locations as indicated by its certifications and markings.