Vött 0063010

Watts 009M2 Reduced Pressure Zone Backflow Preventer (Model 0063010) Instruction Manual

For Models: 009M2, 009M2-QT

1. Inngangur

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Mikilvægar öryggisupplýsingar

3. Vöru lokiðview og íhlutir

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Uppsetning og uppsetning

  1. Athugun fyrir uppsetningu:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Inspect the unit for any shipping damage.
    • Ensure all necessary tools and materials for installation are available.
  2. Undirbúningur síða:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Lagnatenging:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Athugun eftir uppsetningu:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Athugaðu allar tengingar fyrir leka.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Notkunarleiðbeiningar

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Viðhald

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Bilanagreining

VandamálMöguleg orsökLausn
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Enginn vatnsrennsli eða minnkað rennsli
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Leki frá tengingum
  • Improperly sealed threads
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • Skoðið og skiptið um þéttingar.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Tæknilýsing

Gerðarnúmer0063010 (009M2)
Backflow Preventer TypeLækkað þrýstingssvæðissamsetning
LíkamsefniBrons
Stærð inntaks-/úttakstengingar2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Hámarksvinnuþrýstingur175 PSI (12.10 BAR)
Hámarkshiti180°F (82°C)
lágmarkshita33°F (0.5°C)
Tegund verndarBackpressure and Backsiphonage
Vörumál (L x B x H)22 x 10 x 8 tommur
Þyngd hlutar27 pund
Lead Free StatusNO (For non-potable use only)

9. Ábyrgð og stuðningur

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Websíða: www.watts.com

Tengd skjöl - 0063010

Preview Watts LF909 serían fyrir samsetningarverkfræði með minnkuðum þrýstingssvæðum
Ítarleg verkfræðilýsing fyrir Watts LF909 seríuna af þrýstingslækkuðu svæðissamstæðunni (21⁄2" - 10"). Ítarlegar upplýsingar um eiginleika, notkun, efni, mál og afkastagetu þessa blýlausa bakflæðisvarnatækis með innbyggðum flóðaskynjara.
Preview Watts serían 009, LF009, LFU009, SS009, U009: Uppsetningar-, viðhalds- og viðgerðarhandbók
This comprehensive manual from Watts provides essential guidance for the installation, maintenance, and repair of the Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies. It details safety warnings, installation procedures, inspection, servicing, troubleshooting, and warranty information for these critical backflow prevention devices.
Preview Uppsetningar-, viðhalds- og viðgerðarhandbók fyrir Watts seríurnar 909, LF909, 909RPDA með þrýstingslækkuðu svæði
Ítarleg leiðbeiningar um uppsetningu, viðhald og viðgerðir á Watts Series 909, LF909 og 909RPDA þrýstingslækkuðum svæðum, þar á meðal öryggisviðvaranir, uppsetningarleiðbeiningar, prófunaraðferðir, viðhaldsleiðbeiningar, bilanaleit og ábyrgðarupplýsingar.
Preview Watts serían LF909 samsetningar með minni þrýstingssvæði - Tæknilegar upplýsingar
Ítarlegar tæknilegar upplýsingar um Watts Series LF909 samsetningar með þrýstingslækkuðu svæði, þar á meðal eiginleika, notkun, mál, þyngd og afkastagetu. Hannað fyrir stjórnun á krosstengingu drykkjarvatns.
Preview Watts Series 009, LF009, LFU009, SS009, U009 Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Preview Watts Series LF919 samsetning með minnkuðum þrýstingi: Uppsetningar-, viðhalds- og viðgerðarhandbók
Ítarleg leiðbeiningar um uppsetningu, viðhald og viðgerðir á Watts Series LF919 þrýstingslækkuðu svæðissamstæðunni (1/2" - 2"). Inniheldur öryggisviðvaranir, uppsetningarferli, viðhaldsleiðbeiningar og bilanaleit.