EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A User Manual

Brand: EARU | Model: EARU-1012

1. Inngangur

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A. Please read this manual thoroughly before installation and operation to ensure proper functionality and to prevent damage or injury.

The ATS is designed to provide uninterrupted power by automatically transferring loads between phases in a three-phase supply system. It features intelligent monitoring and protection against phase failure, over/under voltage, and overcurrent conditions, ensuring the stability and safety of connected equipment.

2. Öryggisupplýsingar

VIÐVÖRUN: Hætta á raflosti. Uppsetning og viðhald ætti aðeins að vera framkvæmt af hæfu starfsfólki.

  • Always disconnect power before installing or servicing the ATS.
  • Gakktu úr skugga um að allar raflagnir séu í samræmi við staðbundnar og landsbundnar rafmagnsreglur.
  • Staðfestu rétta binditage og straumgildi áður en tækið er tengt.
  • Ekki nota tækið ef það virðist skemmt.
  • Keep children away from electrical equipment.

3. Vöru lokiðview

The EARU Electric 3-Phase ATS is an intelligent device that continuously monitors your three-phase power supply. It automatically switches single-phase loads to a healthy phase in case of a phase failure or imbalance, ensuring continuous operation of critical equipment.

3.1. Innihald pakka

  • 1 x EARU Electric 3-Phase Auto Transfer Switch (ATS)

3.2. Front Panel and Indicators

Front panel of EARU Electric 3-Phase ATS with digital display and control buttons

Myndlýsing: The front panel of the ATS features a digital display showing voltage for L1, L2, L3 phases and current for L1. Below the display are indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I). Control buttons include 'SET' (Menu key), 'Digit+/Up', 'Digit-/Down', and 'Manual ON/OFF' (Power button).

The digital display provides real-time voltage readings for each phase (L1, L2, L3) and the current for L1. Status indicators alert you to the operational state and any detected faults:

  • Kraftur: Output indication.
  • >V: Yfir-voltage vísbending.
  • <V: Undir-voltage vísbending.
  • > ég: Over-current indication.

Control buttons allow for parameter settings and manual operation:

  • SETJA: Menu key for accessing settings.
  • Digit+/Up: Increases value or navigates up in menus.
  • Digit-/Down: Decreases value or navigates down in menus.
  • Handvirkt ON/OFF: Power button for manual control.

4. Uppsetning og uppsetning

The ATS is designed for standard DIN rail mounting. Ensure sufficient space for ventilation and wiring connections.

4.1. Raflið

Wiring diagram for EARU Electric 3-Phase ATS showing input and output connections

Myndlýsing: A detailed wiring diagram illustrates the connection points for the ATS. The top terminals are labeled 'IN' with connections for N, L1, L2, L3. The bottom terminals are labeled 'OUT' with connections for N and L1. The diagram shows how to connect the three-phase input to the ATS and how a single-phase load (L1 and N) is connected to the output, with internal connections for phase monitoring and switching.

Follow the wiring diagram carefully. Incorrect wiring can lead to device malfunction or electrical hazards.

  • Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals.
  • Connect the single-phase load (N, L1) to the 'OUT' terminals. The ATS will manage the phase transfer for the L1 output.
  • Ensure all connections are secure and tightened to prevent loose contacts and overheating.

4.2. Upphafleg ræsing

After completing the wiring, restore power to the system. The ATS will power on and begin monitoring the phases. The digital display will show the current voltage readings for each phase. If all phases are stable and within acceptable limits, the ATS will provide power to the output.

5. Notkunarleiðbeiningar

The ATS operates automatically, but you can adjust its protection parameters to suit your specific requirements.

5.1. Að skilja skjáinn og vísana

The digital display continuously shows the real-time voltage of each phase (L1, L2, L3) and the current on L1. The indicator lights provide quick visual feedback on the device's status and any detected anomalies.

Close-up of EARU Electric 3-Phase ATS digital display showing voltage and current readings

Myndlýsing: Nærmynd view of the ATS digital display. It shows '220V' for L1, L2, and L3, and '63.0A' for L1 current. Below these readings are small indicator icons for Power, >V (Over-voltage), <V (Under-voltage), and >I (Over-current).

5.2. Adjusting Protection Parameters

Use the 'SET' button to enter the parameter setting mode. Use the 'Digit+/Up' and 'Digit-/Down' buttons to navigate through settings and adjust values. Press 'SET' again to confirm and save changes.

Adjustable Protection Parameters
ParameterStillingarsviðSjálfgefin stilling
Over Current Protection Setting Range1-63A/100A30A
Continuous Over Current Protection Times0-20 sinnumSLÖKKT
Yfir Voltage Protection Setting Range230-300V270V
Yfir Voltage Protection Recover Setting Range225-295V265V
Undir Voltage Protection Setting Range140-210V170V
Undir Voltage Protection Recover Setting Range145-215V175V
Voltage & Current Protection Recover Delay1-500 sek30s

5.3. Automatic Phase Transfer

The ATS automatically monitors the three input phases (L1, L2, L3). If a phase failure or significant voltage imbalance (over/under voltage) is detected on the currently supplying phase, the device will automatically transfer the single-phase output load to a healthy, stable phase within the same supply. This process is designed to be seamless and rapid, minimizing power interruption to connected equipment.

5.4. Automatic Recovery

Once the primary phase recovers and stabilizes, the ATS will intelligently switch the load back to the primary source, ensuring optimal power distribution and preventing equipment damage from unstable power. The recovery delay can be configured as per your operational needs.

6. Viðhald

The EARU Electric ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.

  • Þrif: Haldið tækinu hreinu og lausu við ryk og óhreinindi. Notið þurran, mjúkan klút til að þrífa. Notið ekki fljótandi hreinsiefni.
  • Tengingarathuganir: Periodically inspect all wiring connections to ensure they remain tight and free from corrosion.
  • Umhverfisskilyrði: Gakktu úr skugga um að rekstrarumhverfið sé innan tilgreindra hitastigs- og rakastigsbila.

7. Bilanagreining

If you encounter issues with your ATS, refer to the following common problems and solutions:

Úrræðaleit Guide
VandamálMöguleg orsökLausn
Ekkert aflframleiðslaNo input power; all phases unstable; device in fault state.Check incoming power supply. Verify all phases are stable. Check fault indicators.
">V" or "<V" indicator litYfir-voltage eða undir-bindtage detected on a phase.Athugaðu inntak voltage stability. The ATS will automatically transfer if another phase is healthy.
">I" indicator litOver-current detected on the output.Reduce load on the output. Check for short circuits in the connected equipment.
Device not transferring phasesNo healthy alternative phase available; transfer delay setting too long.Ensure at least one healthy phase is present. Check and adjust the transfer delay settings.
Stafrænn skjár virkar ekkiNo power to the device; internal fault.Check power supply. If power is present and display is off, contact support.

For issues not covered here, please contact EARU customer support.

8. Tæknilýsing

Detailed specifications and dimensions of EARU Electric 3-Phase ATS

Myndlýsing: This image displays the physical dimensions of the ATS (90mm width, 96mm height, 66mm depth) and a table of detailed technical specifications, including current rating, voltage, frequency, and various protection setting ranges.

EiginleikiSmáatriði
VörumerkiEARU
GerðarnúmerEARU-1012
NotkunarhamurKveikt
Núverandi einkunn63 Amps
Operation Voltage440 Volts (AC 3*220V (N-L1/L2/L3))
Máltíðni50/60Hz
Tegund tengiliðaVenjulega opið
Tegund tengisStandard DIN rail 63A
Rás hringrásar4-átta
Hafðu samband við efniKopar
Over Current Protection Setting Range1-63A/100A (Default 30A)
Continuous Over Current Protection Times0-20 Times (Default OFF)
Yfir Voltage Protection Setting Range230-300V (Sjálfgefið 270V)
Yfir Voltage Protection Recover Setting Range225-295V (Sjálfgefið 265V)
Undir Voltage Protection Setting Range140-210V (Sjálfgefið 170V)
Undir Voltage Protection Recover Setting Range145-215V (Sjálfgefið 175V)
Voltage & Current Protection Recover Delay1-500s (Default 30s)
Þyngd hlutar450 g
Stærðir pakka15 x 15 x 15 cm
UpprunalandIndlandi

9. Ábyrgð og stuðningur

9.1. Upplýsingar um ábyrgð

The EARU Electric 3-Phase Auto Transfer Switch (ATS) comes with a 1 árs ábyrgð framleiðanda from the date of purchase. This warranty covers defects in materials and workmanship under normal use. It does not cover damage caused by improper installation, misuse, accidents, or unauthorized modifications.

9.2. Þjónustudeild

For technical assistance, warranty claims, or any questions regarding your EARU Electric ATS, please contact your retailer or the manufacturer directly. Ensure you have your product model number (EARU-1012) and proof of purchase available when contacting support.

Tengd skjöl - EARU-1012

Preview EARU GFGQX-63 Three-Phase Digital Adjustable Reclosing Protector User Manual
User manual for the EARU GFGQX-63 Three-Phase Digital Adjustable Reclosing Protector. This device provides over/under voltage, over current, phase sequence, and phase imbalance protection with automatic reclosing functionality. Includes detailed specifications, settings, and wiring instructions.
Preview EARU Automatic Transfer Switch (ATS) Operating Instruction and Technical Specifications
Comprehensive operating instructions and technical specifications for the EARU Automatic Transfer Switch (ATS) model EAATS-F-CG-80. Covers product overview, working conditions, model breakdown, detailed technical parameters, installation guidelines, maintenance procedures, and wiring diagrams.
Preview EARU EAPDX-40/63 Series Adjustable VoltagNotendahandbók fyrir e & straumvörn
User manual for the EARU EAPDX-40/63 Series Adjustable Voltage & Current Protector, detailing specifications, features, and operation for electrical protection. Includes setup instructions and parameter configuration.
Preview EARU-X6/8 Metal LED Indicator Light Instruction Manual
User manual for EARU-X6/8 series Metal LED Indicator Lights, detailing safety instructions, warnings, and product description for reliable status indication in industrial and traffic applications.
Preview EARU KR0548-CH WiFi Smart Automatic Transfer Switch (ATS) User Manual
User manual for the EARU KR0548-CH WiFi Smart Automatic Transfer Switch (ATS). Learn how to install, connect, and operate the device using the EARU app for seamless switching between main and backup power sources.
Preview PC321-Z-TY Einfasa/Þriggja fasa aflgjafarklefiamp Flýtileiðarvísir
Get started with the EARU PC321-Z-TY Smart Power Clamp. This guide covers installation, configuration, and features for monitoring single/3-phase electricity usage with ZigBee connectivity and the Smart Life app.