L-com SRAQ-D701 fjölnota loftgæðaskynjaraeining

Vörulýsing

The SRAQ-D701 is a comprehensive air quality sensor module which combines CO², laser dust, temperature and humidity, TVOC and formaldehyde.
Developed for integration into air purifiers, air quality monitors and custom enclosures. The SRAQ-D701 provides real time concentration values via Modbus-RTU output. It offer good stability, and is well suited for applications where TVOC and particulate matter concentrations are a concern.

Eiginleikar

  • Detects multiple pollutants CO2, dust etc.
  • Modbus úttak
  • High reliability and good stability
  • High accuracy & fast response
  • Fyrirferðarlítil hönnun til að auðvelda samþættingu

Umsóknir

  • Office and commercial buildings
  • Factory floors
  • Rannsóknastofur
  • HAVC industry
  • General air quality monitoring
  • Smart home systems

Thank you for choosing L-com product. To ensure safe, accurate performance and product longevity, please take a moment to familiarize yourself with this manual before powering the device. Please keep it handy for future reference. In case of any questions regarding the installation or use of product, please call us at 800.341.5266.
Hafðu samband við okkur kl customerservice@l-com.com og heimsækja okkar websíða kl www.l-com.com

This datasheet has been downloaded from http://www.digchip.com á þessu síðu

Tæknilegar breytur

Greiningarbreytur og upplausn: CO2 gildið og formaldehýð gildið sem mælt er með einingunni eru jafngild TVOC gildi, vinsamlegast athugið það þegar það er notað eða keypt.

Mengandi efni Mælingarupplausn Mælisvið Nákvæmni
eCO2 1 ppm 400~5000 ppm ± 100 ppm
PM2.5 0.3 ug/m3 0~1000 ug/m3 ± 10%
PM10 0.3 ug/m3 0~1000 ug/m3 ± 10%
Hitastig 0.01 °C 20 ~ 80 ° C ± 0.5 °C
Raki 0.04% 5~100% RH ± 3% RH
TVOC 1 ug/m3 1230 ug/m3 ± 90 ug/m3
CH2O 1 ug/m3 500 ug/m3 ± 40 ug/m3
  1. Vinna voltage: 5 ± 0.2 VDC
  2. Working environment: Working temperature 0~50 °C, Working humidity: 15% RH  90% RH (no condensation)
  3. Working environment: Temperature range -20~60 °C, Humidity: 5% RH  95% RH (no condensation)
  4. Communication method: Modbus RTU  RS485
  5. Preheating time: 10-15 minutes, the longer the power-on time, the more stable the data will be.

Uppsetningarmyndir

Festingartegund: Festing á borðplötu. Gatþvermál 2 mm, gatbil 11.5 mm.

L-com SRAQ-D701 Multifunction Air Quality Sensor Module - Mounting Diagrams

Vírskilgreining

Tengitegundin er XH2.54 mm 4 pinna tengi, fest 90° lóðrétt á prentplötu.

Sr. nr. Virka Skýringar Litur
1 VCC 12 – 24 VDC, power supply positive Brúnn
2 GND GND, neikvæð aflgjafa Svartur
3 RS485_A+ RS485_A+ Grænn
4 RS485_B- RS485_B- Blár

Samskiptabókun

The module hardware supports serial TTL communication interface and RS485 communication interface. When testing, users need to choose the corresponding communication method development according to the module interface type they have purchased.
RS485 Interface Communication Interface Related Protocol:
Serial port parameters: (9600/8/N/1) Mod Bus-RTU 485
The factory default address of the module is 0x01
Baud rate: 9600, Check bit: no, Stop position: 1 bit
Return data time: <300ms
The reading speed cannot exceed 350ms

Lestu skipunina „Lesa heimilisfang“

Taka á móti Lagað Aðgerðarnúmer Lagað Lagað Lagað Lagað CRC_L CRC_H
FE 17 00 00 00 01 CRC athuga
Svaraðu Lagað Aðgerðarnúmer Fjöldi bæta Firmware útgáfa Núverandi heimilisfang CRC_L CRC_H
FE 17 02 xx yy CRC athuga

Til dæmisample: Send command: FE 17 00 00 00 01 A0 06 Return data: FE 17 02 11 01 64 30
Indicates that the device address is 01 and the version number is V1.1
Skipunin Breyta heimilisfangi
Sjálfgefið vistfang einingarinnar frá verksmiðju er 0x01 og hægt er að breyta vistfangssviðinu í: 0~254.

Taka á móti Núverandi heimilisfang Aðgerðarnúmer Lagað Lagað Frátekið Sjálfgefið heimilisfang CRC_L CRC_H
yy 06 00 00 00 zz CRC athuga
Svaraðu Address Before Modification Aðgerðarnúmer Fjöldi bæta Halda Modified Address CRC_L CRC_H
yy 06 02 00 Zz CRC athuga

Til dæmisample: When the current address is 01, the preset address is: 02
Send command: 01 06 00 00 00 02 08 0B Return data: 01 06 02 00 02 39 49
Lestu gögn skipunina

Taka á móti Núverandi heimilisfang Aðgerðarnúmer Skrá upphafs heimilisfang Fjöldi skynjara sem þarf til að lesa CRC_L CRC_H
yy 03 00 MM 00 NN CRC athuga
Svaraðu Núverandi heimilisfang Aðgerðarnúmer Gagnalengd Skynjaragögn CRC_L CRC_H
yy 03 NN*2 xx xx ……xx xx CRC athuga

Note: The returned xx xx ……xx xx sensor data can be changed according to the register address and data length.
00 MM represents the register address of the sensor, and 00 NN is the data length.

Register address(00 MM)
00 00 00 01 00 02 00 03 00 04 00 05 00 06
eCO2 TVOC CH2O PM2.5 Raki Hitastig PM10

Lýsing

  1. The minimum number of sensors 00 NN is 00 01, and the maximum is 00 07. When the MM value is 00, the maximum NN value can be 07. At this time, the value of all sensors can be read, and it can also be 01. When it is 01, only CO2 data can be read alone. And so on.
  2. The address at the front of the register can read the data of the following sensor when the data length is increased, but the address at the back of the register cannot read the data of the sensor before this address. See details below:
00 MM 00 NN Umhverfisgögn sem hægt er að lesa
00 00 00 01 Indicates that CO2 data is read from the starting address 00 00
00 00 00 02 Means to read CO2, TVOC data from the starting address 00 00
00 00 00 03 Means to read CO2, TVOC, CH2O data from the starting address 00 00
00 00 00 04 Means to read CO2, TVOC, CH2O, PM2.5 data from the starting address 00 00
00 00 00 05 Means to read CO2, TVOC, CH2O, PM2.5, H data from the starting address 00 00
00 00 00 06 Means to read CO2, TVOC, CH2O, PM2.5, H, T data from the starting address 00 00
00 00 00 07 Means to read CO2, TVOC, CH2O, PM2.5, H, T, PM10 data from the starting address 00 00
00 01 00 01 Indicates that the TVOC data is read from the starting address 00 01
00 01 00 02 Indicates that TVOC and CH2O data are read from the starting address 00 01
00 01 00 03 Means to read TVOC, CH2O, PM2.5 data from the starting address 00 01
00 01 00 04 Means to read TVOC, CH2O, PM2.5, H data from the starting address 00 01
00 01 00 05 Means to read TVOC, CH2O, PM2.5, H, T data from the starting address 00 01
00 01 00 06 Means to read TVOC, CH2O, PM2.5, H, T, PM10 data from the starting address 00 01
00 02 00 01 Indicates that CH2O data is read from the starting address 00 02
00 02 00 02 Indicates that CH2O and PM2.5 data are read from the starting address 00 02
00 02 00 03 Means to read CH2O, PM2.5, H data from the starting address 00 02
00 02 00 04 Means to read CH2O, PM2.5, H, T data from the starting address 00 02
00 02 00 05 Means to read CH2O, PM2.5, H, T, PM10 data from the starting address 00 02
00 03 00 01 Gefur til kynna að PM2.5 gögn séu lesin frá upphafsstaðsetningunni 00 03
00 03 00 02 Leiðir til að lesa PM2.5, H gögn frá upphafsstaðsetningunni 00 03
00 03 00 03 Leiðir til að lesa PM2.5, H, T gögn frá upphafsstaðsetningunni 00 03
00 03 00 04 Leiðir til að lesa PM2.5, H, T, PM10 gögn frá upphafsstaðsetningunni 00 03
00 04 00 01 Gefur til kynna að H-gögnin séu lesin frá upphafsvistfanginu 00 04
00 04 00 02 Leiðir til að lesa H, T gögn frá upphafsfanginu 00 04
00 04 00 03 Leiðir til að lesa H, T, PM10 gögn frá upphafsstaðsetningunni 00 04
00 05 00 01 Gefur til kynna að T-gögnin séu lesin frá upphafsvistfanginu 00 05
00 05 00 02 Leiðir til að lesa T, PM10 gögn frá upphafsfanginu 00 05
00 06 00 01 Gefur til kynna að PM10 gögn séu lesin frá upphafsfanginu 00 06

Hvernig á að lesa gagnaramma
Til dæmisample, if the address of the module is 0x01, the user needs to send 01 03 00 00 00 07 04 08 to read out seven kinds of sensor data.
The returned data format is as follows:

Bæti[0] Bæti[1] Bæti[2] Bæti[3] Bæti[4] Bæti[5] Bæti[6] Bæti[7] Bæti[8]
Haus Aðgerðarnúmer Gagnalengd CO2 Gögn TVOC gögn CH2O Data
0x01 0x03 0x0E CO2_H CO2_L TVOC_H TVOC_L CH2O_H CH2O_L
Bæti[9] Bæti[10] Bæti[11] Bæti[12] Bæti[13] Bæti[14] Bæti[15] Bæti[16] Bæti[17] Bæti[18]
PM2.5 Gögn Rakastig gögn Hitastigsgögn PM10 Gögn CRC16 Athugaðu
PM2.5_H PM2.5_L Hum_H Hum_L Tem_H Tem_L PM10_H PM10_L CRC16_L CRC16_H

Útreikningsaðferð fyrir hverja skynjaragögn
CO2 (ppm) = CO2 _H * 256 + CO2 _L
TVOC(ug/m3) = (TVOC_H * 256 + TVOC_L) / 10
CH2O(ug/m3) = (CH2O_H * 256 + CH2O_L) / 10
PM2.5 (ug/m3) = PM2.5_H * 256 + PM2.5_L
PM10 (ug/m3) = PM10_H * 256 + PM10_L
Positive temperature (°C) = (Temperature _H * 256 + Temperature_ L) / 10
Til dæmisample: T = (0 x 0110) / 10 = 272 / 10 = 27.2 ℃

Neikvætt hitastig (°C)
Aðferð 1: Umbreyta beint í undirritað heiltölutegund, til dæmisample: T = 0 x ffbf / 10 = -65 / 10 = -6.5 ℃
Method 2: If greater than 0 x 7fff (32767)
Then it is a negative number T = (0 x ffbf – 65536) / 10 = (65471 – 65536) / 10 = -65 / 10 = -6.5 ℃
Humidity (%RH) = (Humidity _H * 256 + Humidity _L) / 10
Til dæmisample: T = (0 x 02AD) / 10 = 685 / 10 = 68.5 %RH
Note: If user need to use mg/m3 as the unit, please convert it. The conversion formula is: 1mg/m3 =1000 ug/m3
The length of the CRC check byte is 17 (that is, the bytes of Byte[0]~Byte[16]), select A001 or 8005 in reverse order.

Mál sem þarfnast athygli

  1. Avoid contact with organic solvents (including silica gel and other adhesives), paints, pharmaceuticals, oils and high-concentration gases.
  2. The module must not be subjected to excessive shock or vibration.
  3. Ekki nota þessa einingu á kerfi sem fela í sér persónulegt öryggi.
  4. Ekki setja eininguna upp í sterku lofthitunarumhverfi.

Útreikningsaðferð fyrir CRC-athugun
Function function: CRC check function, generate CRC
Parameter description: arr_ buff: array set to be verified
len: The length of the data to be verified
Return parameter: CRC is an unsigned int type, the high byte is the high byte in front, and the low byte is in the back unsigned int CRC_ Compute ( unsigned char *arr_ buff, unsigned char len)
{
unsigned int crc=0xFFFF;
óundirritaður bleikja i, j;
for ( j=0; j <len;j++)
{
crc=crc ^*arr_buff++;
for ( i=0; i<8; i++)
{
if( ( crc&0x0001) >0)
{
crc=crc>>1;
crc=crc^ 0xa001;
}
annað
crc=crc>>1;
}
}
return ( crc);
}