Notendahandbók – Modbus
EMX-IP – User Interface and Modbus
Samskiptaleiðbeiningar
Senva skynjarar
1825 NW 167th PL
Beaverton, OR 97006
154-0050-0A
EMX-IP notendaviðmót og Modbus
sr. | Gefa út Dagsetning | By | Lýsing of Breyta | ECR |
0A | 10/14/2024 | CJL | Upphafleg útgáfa | 01350 |
— | ||||
— | ||||
— | ||||
Höfundarréttur ©2025. Allur réttur áskilinn. Þetta skjal inniheldur eignarupplýsingar Senva Sensors og má ekki afrita eða dreifa án skriflegs leyfis.
Sjá einnig:
152-0430 EMX-IP Installation Instructions
154-0049 EMX-IP BACnet Protocol Guide
154-0051 EMX-IP Navigation Guide
Congratulations on installing your new Senva EMX-IP energy meter! This Modbus Protocol Guide assumes the first stage of installation is complete, with the meter and any CTs connected and powered. The OLED display should show the home screen when any
button is pressed. If not, refer to the separate Installation Instructions before continuing.
Now, only the network configuration remains between you and the data.
Á hvaða skjá sem er, ýttu á ENTER hnappinn til að fá aðgang að stillingavalmyndinni.
You can make selections using the UP and DOWN arrows and then pressing ENTER to proceed to that menu or setting.
Í hvaða valmynd sem er, ýttu á ESC hnappinn til að fara aftur í eina valmynd.
Til að breyta gildi, notaðu UPP og NIÐUR örvarnar til að stilla hvern tölustaf og ENTER hnappinn til að færa bendilinn til vinstri.
Þegar hver stafur hefur verið stilltur skaltu ýta á ENTER í síðasta sinn til að fara aftur í fyrri valmynd.
Til að hætta við breytingar hvenær sem er geturðu ýtt á ESC.
Setja upp skrár og færibreytur
Uppsetningarskrár og færibreytur eru fáanlegar í 5 hópum í stillingavalmyndinni með því að nota skjáinn eða einnig er hægt að nálgast þær með Modbus fjarskiptum.
Stillingar
Stillingar eru fáanlegar í eftirfarandi hópum á skjánum. Listi yfir færibreytur er að finna í eftirfarandi köflum.
- Mæling – Stilltu mælibreytur eins og rúmmáltage og straumstærð, fasaröðun og skjáeiningar.
- Pulse Config – Read the count of the two pulse inputs.
- Communications – See IPv4 and IPv6 values.
- Viðvörun – Virkja eða slökkva á viðvörun og stilla ferðapunkta.
- Real-Time Clock – Set the date and time.
- Logging – Enable or disable logging as well as setting trigger source and what is logged.
- Aðgangskóði – Veldu aðgangskóða til að læsa tækinu.
- Ítarlegri - View vélbúnaðarútgáfur eða hefja endurstillingu á verksmiðju.
The following sections detail how to adjust settings over the Modbus interface. All settings are stored in non-volatile memory. Stored values will not be lost if the meter experiences a power loss.
H/V:
R = Aðeins læsilegt
R/W = Lesið og skriflegt
Tegund, lágmark, hámark:
ENUM = UINT16 16 bita óundirrituð heiltala sem varparið á skilgreindan lista yfir gildi
U8 = UINT8 8-bit unsigned integer; 0 to 1
U16 = UINT16 16-bit unsigned integer; min/max values listed
I16 = INT16 16-bit integer; -768 to 768
Mælikvarði:
Gildi verða að margfalda með þessum kvarðastuðli til að lesa rétt. 15 * 0.1 = 1.5. Þegar þú skrifar skal deila gildinu með kvarðanum áður en það er skrifað. 1.5 / 0.1 = 15.
Modbus virknikóðar:
The EMX setting registers support the following Modbus function codes:
- 0x03 Lestu eignarskrár
- 0x04 Lesa inntaksskrá
- 0x06 Lesa einbýlisskrá
- 0x10 Write Multiple Holding Registers
Mælir
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Sjálfgefið | Mælikvarði | Einingar | |
Fasa stillingar | 0-3PH ABCN, 1-3PH ABC, 2-1PH ABN, 3-1PH AB, 4-SplitPH ABN |
2000 | R/W | ENUM | 0 | 4 | 0 | N/A | N/A |
Núverandi þáttur | 0-Current Transformer, 1-Rogowski Coil |
2001 | R/W | ENUM | 0 | 1 | 0 | N/A | N/A |
Núverandi mælikvarði | Sjá athugasemd 1 | 2002 | R/W | U16 | 10 | 60000 | 10 | 0.1 | Amps pr 0.333 volt |
Current Orientation | Fyrir stig A, B, C: 0- +, +, + 1- +, +, – 2- +, -, + 3- +, -, – 4- -, +, + 5- -, +, - 6- -, -, + 7- -, -, – |
2003 | R/W | ENUM | 0 | 7 | 0 | N/A | N/A |
Voltage mælikvarði | Sjá athugasemd 2 | 2004 | R/W | U16 | 10 | 32000 | 100 | 0.01 | Einingalaus |
Sýna einingar | 0- IEC Units, 1- IEEE Units |
2005 | R/W | ENUM | 0 | 1 | 1 | N/A | N/A |
- Straumkvarði er aðalhliðarstraumur 0.333V CT. CTs með output voltage exceeding 0.333V should not be used. For a CT ratio of 20A / 0.333 V this will be 20.0 * 10 = 200. If a Rogowski coil is installed this value will need to be calculated from the coils mV/1000A rating. Rogowski conversion is calculated by (333.33 mV / x mV) *1000A * 10(scale).
- Voltage scale is the PT ratio expressed as a decimal and multiplied by 100. A potential transformer of 25:10 would give a ratio of 25 / 10 = 2.5, appropriately scaled it would be 2.5*100 = 250.
Viðvörun
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Sjálfgefið | Mælikvarði | Einingar | |
Viðvörun - Voltage Out of Range Enable | 0-Slökkva 1-Virkja | 2016 | R/W | ENUM | 0 | 1 | 0 | N/A | N/A |
Viðvörun - Voltage Nafnsvið utan sviðs | Set nafnverð LL voltage for out-of- range alarm, least significant digit is 1/10th of a Volt. | 2017 | R/W | U16 | 10 | 60000 | 2400 | 0.1 | Volt |
Viðvörun - Voltage Þröskuldur utan sviðs | Prósentan yfir eða undir nafnrúmmálitage setting (2017) at which a fault will trigger. | 2018 | R/W | U16 | 1 | 20 | 10 | 1 | % |
Alarm – Current Out of Range Enable | 0-Slökkva 1-Virkja | 2019 | R/W | ENUM | 0 | 1 | 0 | N/A | N/A |
Viðvörun – Núverandi utan sviðs | Set nominal current for out-of- range alarm, least significant digit is 1/10th of an Amp. | 2020 | R/W | U16 | 10 | 60000 | 50 | 0.1 | Amps |
Viðvörun – Þröskuldur fyrir núverandi utan sviðs | The percent above or below the nominal current setting (2020) at which a fault will trigger. | 2021 | R/W | U16 | 1 | 20 | 10 | 1 | % |
Alarm Ground Current Out of Range Enable | 0-Slökkva 1-Virkja | 2022 | R/W | ENUM | 0 | 1 | 0 | N/A | N/A |
Viðvörun Jarðstraumur utan marksviðs | Set nominal ground current for out-of-range alarm, least significant digit is 1/10th of an Amp. | 2023 | R/W | U16 | 10 | 60000 | 50 | 0.1 | Amps |
Viðvörun Jarðstraumur utan sviðsþröskulds | The percent above the nominal ground current setting (2023) which a fault will trigger. | 2024 | R/W | U16 | 1 | 20 | 10 | 1 | % |
Alarm Frequency Out of Range Enable | 0-Slökkva 1-Virkja | 2025 | R/W | ENUM | 0 | 1 | 1 | N/A | N/A |
Alarm Frequency Out of Range Nominal | Set nominal frequency for out- of-range alarm, least significant digit is 1/100th of a Hertz. | 2026 | R/W | U16 | 450 | 650 | 600 | 0.1 | Hz |
Alarm Frequency Out of Range Threshold | The percent above or below the nominal frequency setting (2026) at which a fault will trigger. | 2027 | R/W | U16 | 1 | 20 | 10 | 1 | % |
Alarm Voltage Phase Loss Enable | 0-Slökkva 1-Virkja | 2028 | R/W | ENUM | 0 | 1 | 1 | N/A | N/A |
Alarm Voltage Fasa Tap Þröskuldur | Fasa-til-fasa samanburður á LN binditages er framkvæmt. Ef einhver fasa er LN binditage is below the others by the threshold amount, a fault will trigger. Only applicable to 3Φ configurations (ABC or ABCN). Single phase installations will power off during phase loss event. | 2029 | R/W | U16 | 1 | 20 | 10 | 1 | % |
Alarm Voltage Phase Imbalance Enable | 0-Slökkva, 1-Virkja | 2030 | R/W | ENUM | 0 | 1 | 1 | N/A | N/A |
Alarm Voltage Fasa ójafnvægisþröskuldur | The percent of phase-to-phase imbalance above which a fault will trigger. For a three-phase Y system, both VL-L and VL-N are examined. For a three-phase delta, only VL-L measurements are compared. In a single split- phase, only VL-N are compared. | 2031 | R/W | U16 | 1 | 20 | 10 | 1 | % |
Viðvörun Power Factor Low Virkja | 0-Slökkva 1-Virkja | 2032 | R/W | ENUM | 0 | 1 | 1 | 1 | N/A |
Viðvörunaraflsstuðull lágur þröskuldur | Stilltu (einingalausa) PF gildið, undir því mun bilun kvikna. | 2033 | R/W | U16 | 1 | 99 | 50 | 0.01 | Einingalaus |
Ítarlegri
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Sjálfgefið | |
Endurstilla Wh | Writing 1 will reset all the stored Wh, VAh and VARh values. | 2034 | R/W | U16 | 0 | 1 | 0 |
Fjöldi Wh endurstillir | Fjöldi skipta sem Wh hefur verið endurstillt. | 2035 | R | U16 | 0 | 65535 | 0 |
Endurstilla keyrslutíma |
Að skrifa 1 mun endurstilla keyrslutíma kerfisins (37 og 38), en ekki kerfisvirkjunartímann (35 og 36). | 2036 | R/W | U16 | 0 | 1 | 0 |
Talning keyrslutíma Endurstillir | Fjöldi skipta sem keyrslutími kerfisins hefur verið endurstilltur. | 2037 | R | U16 | 0 | 65535 | 0 |
Endurstilla púlstölur | Writing 1 will reset the pulse input counters (41 through 44). | 2038 | R/W | U16 | 0 | 1 | 0 |
Reboot EMX | Reboots the EMX. When written, this point may not give a response or may return an error due to the reset process. The point will still accept the value. | 2042 | R/W | U8 | 0 | 1 | 0 |
Reset Log Content | Writing a 1 value to this register reset all the stored log entries. This will break communications and display connection for approx. 25 seconds. Do not remove power during this update. When written, this point may not give a response or may return an error due to the reset process. The point will still accept the value. | 2043 | R/W | U16 | 0 | 1 | 0 |
Phase Angle Compensation | 2044 | R/W | I16 | -768 | 768 | 0 | |
Lykilorð | Set display passcode | 2045 | R/W | U16 | 0 | 9999 | 0 |
Metering Registers
The following table describes each of the power and energy readings provided over Modbus from the device.
H/V:
R = Read Only
R/W = Lesa og skrifa
Tegund, lágmark, hámark:
ENUM = UINT16 16 bita óundirrituð heiltala sem varparið á skilgreindan lista yfir gildi
U8 = UINT8 8-bit unsigned integer; 0 to 255, unless otherwise noted
U16 = UINT16 16-bit unsigned integer; 0 to 65535 (0xFFFF), unless otherwise noted
I16 = INT16 16-bit integer; -32768 to 32767, unless otherwise noted
U32 = UINT32 32-bit unsigned integer; 0 to 4294967295 (0xFFFFFFFF), unless otherwise noted
U64 = UINT64 64-bit unsigned integer; 0 to 18.466e+18
I64 = INT64 64-bit signed integer; -9.233e+18 to 9.233e+18
Mælikvarði:
Gildi verða að margfalda með þessum kvarðastuðli til að lesa rétt. Fyrir sumt afl, straum og voltage lestur, mælikvarðastuðullinn verður sjálfkrafa stilltur miðað við notendastillingar fyrir voltage og núverandi mælikvarði. Þessa margfaldara má lesa í skrám 030-032.
Verslun:
Gildi merkt „já“ verða geymd í óstöðugt minni. Geymd gildi munu ekki glatast ef mælirinn verður fyrir rafmagnsleysi.
Modbus virknikóðar:
The EMX metering registers support the following Modbus function codes:
- 0x03 Lestu eignarskrár
- 0x04 Lesa inntaksskrá
Some registers span multiple Modbus addresses. Two consecutive registers defined as XXX/YYY indicates a pair of aligned registers, that must be merged into a 32-bit value.
Four consecutive registers require merging the results into a 64-bit value. See data type conversions section for more information and examples.
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun | |
V-LN meðaltal | 001 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
V-LL meðaltal | 002 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
Núverandi meðaltal | 003 | R | U16 | 0 | 65535 | I-skala | Hendur) | Nei | |
Núverandi Summa | 004 | R | U16 | 0 | 65535 | I-skala | Hendur) | Nei | |
Raunverulegur kraftur samtals | 005 | R | I16 | -32768 | 32767 | P-kvarði | W | Nei | |
Viðbragðsafl samtals | 006 | R | I16 | -32768 | 32767 | P-kvarði | VAR | Nei | |
Sýnilegur kraftur alls | 007 | R | I16 | -32768 | 32767 | P-kvarði | VA | Nei | |
V-LN áfangi A | 008 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
V-LN áfangi B | 009 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
V-LN áfangi C | 010 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
V-LL Phase AB | 011 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
V-LL áfangi BC | 012 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
V-LL áfangi CA | 013 | R | U16 | 0 | 65535 | V-kvarði | V(rms) | Nei | |
Núverandi áfangi A | 014 | R | U16 | 0 | 65535 | I-skala | Hendur) | Nei | |
Núverandi áfangi B | 015 | R | U16 | 0 | 65535 | I-skala | Hendur) | Nei | |
Núverandi áfangi C | 016 | R | U16 | 0 | 65535 | I-skala | Hendur) | Nei | |
Aflstuðull A áfangi | 017 | R | I16 | -1000 | 1000 | 0.001 | Einingalaus | Nei | |
Power Factor Fasi B | 018 | R | I16 | -1000 | 1000 | 0.001 | Einingalaus | Nei | |
Power Factor Fasi C | 019 | R | I16 | -1000 | 1000 | 0.001 | Einingalaus | Nei | |
Tíðni (áfangi A) | 020 | R | U16 | 480 | 620 | 0.1 | Hz | Nei | |
Raunorkustig A | 021 | R | I16 | 32768 | 32767 | P-kvarði | W | Nei | |
Raunorkustig B | 022 | R | I16 | 32768 | 32767 | P-kvarði | W | Nei | |
Raunorkustig C | 023 | R | I16 | 32768 | 32767 | P-kvarði | W | Nei | |
Hvarfkraftur Fasi A | 024 | R | I16 | 32768 | 32767 | P-kvarði | VAR | Nei | |
Hvarfkraftur Fasi B | 025 | R | I16 | 32768 | 32767 | P-kvarði | VAR | Nei | |
Hvarfkraftur Fasi C | 026 | R | I16 | 32768 | 32767 | P-kvarði | VAR | Nei | |
Sýnilegur kraftur A áfangi | 027 | R | I16 | 32768 | 32767 | P-kvarði | VA | Nei | |
Sýnilegt afl áfangi B | 028 | R | I16 | 32768 | 32767 | P-kvarði | VA | Nei | |
Sýnilegt afl áfangi C | 029 | R | I16 | 32768 | 32767 | P-kvarði | VA | Nei | |
Voltage Mælikvarði Þáttur (V-scale) |
-4:0.0001 -3:0.001 -2:0.01 -1:0.1 0:1 1:10 2:100 3:1000 4:10000 5:100000 6:1000000 |
030 | R | I16 | -2 | 2 | 1 | N/A | Nei |
Núverandi Mælikvarði Þáttur (I-scale) |
031 | R | I16 | -3 | 1 | 1 | N/A | Nei | |
Kraftur Mælikvarði Þáttur (P-scale) |
032 | R | I16 | -4 | 6 | 1 | N/A | Nei |
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun | |
Viðvörunarstaða bitasviðs | Bit 0: Pulse configuration error Bit 1: Pulse overrun error Bit 2: Voltage utan sviðs Bit 3: Straumur utan sviðs Bit 4: Current sum (neutral current) out of range Bit 5: Freq. out of range Bit 6: Voltage áfanga tap Bit 7: Voltage fasa ójafnvægi Bit 8: Aflstuðull lágur Bit 9: Accumulator loss Bit 10: RTC error Bit 11: Logs full Bit 12: Meter settings error Bit 13 – 15: Reserved |
033 | R | U16 | 0 | 0xFFFF | 1 | N/A | Nei |
Hlaða Staða | 0: No load detected 1: Load above threshold |
034 | R | ENUM | 0 | 1 | 1 | N/A | Nei |
Kerfisstyrkur á réttum tíma | 035 036 |
R | U32 | 0 | 4294967295 | 1 | Sekúndur | Já | |
Keyrslutími kerfis | 037 038 |
R | U32 | 0 | 4294967295 | 1 | Sekúndur | Já | |
Power Reset Count | 039 040 |
R | U32 | 0 | 4294967295 | 1 | N/A | Já | |
Púlstalning 1 | 041 042 |
R | U32 | 0 | 4294967295 | 1 | N/A | Já | |
Púlstalning 2 | 043 044 |
R | U32 | 0 | 4294967295 | 1 | N/A | Já | |
Raunveruleg netorka samtals | 045 046 047 048 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | Wh | Já | |
Raunveruleg netorka Fasi A | 049 050 051 052 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | Wh | Já | |
Raunveruleg netorka Fasi B | 053 054 055 056 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | Wh | Já |
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun |
Raunveruleg netorka Fasi C | 057 058 059 060 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | Wh | Já |
Reactive Nettóorka samtals | 061 062 063 064 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VARh | Já |
Viðbragðs nettóorka A. stig | 065 066 067 068 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VARh | Já |
Hvarfandi netorka Fasi B | 069 070 071 072 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VARh | Já |
Viðbragðs nettóorka Fasi C | 073 074 075 076 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VARh | Já |
Sýnileg hrein orka samtals | 077 078 079 080 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VAh | Já |
Sýnileg nettóorka áfangi A | 081 082 083 084 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VAh | Já |
Sýnileg hrein orka áfangi B | 085 086 087 088 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VAh | Já |
Sýnileg nettóorka áfangi C | 089 090 091 092 |
R | I64 | -9.233e+18 | 9.233e+18 | 0.00000001 | VAh | Já |
Rauninnflutningsorka samtals | 093 094 095 096 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Rauninnflutningsorka Fasi A | 097 098 099 100 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Rauninnflutningsorka Fasi B | 101 102 103 104 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Rauninnflutningsorka Fasi C | 105 106 107 108 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun |
Reactive Import Energy samtals | 109 110 111 112 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Hvarfandi innflutningsorka A áfangi | 113 114 115 116 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Hvarfandi innflutningsorka Fasi B | 117 118 119 120 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Hvarfandi innflutningsorka Fasi C | 121 122 123 124 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Sýndar innflutningsorka samtals | 125 126 127 128 |
R |
U64 |
0 |
18.446e+18 |
0.00000001 |
VAh |
Já |
Augljós innflutningsorka A. stig | 129 130 131 132 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Augljós innflutningsorka Fasi B | 133 134 135 136 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Augljós innflutningsorka áfangi C | 137 138 139 140 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Raunútflutningsorka samtals | 141 142 143 144 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Raunútflutningsorka Áfangi A | 145 146 147 148 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Raunútflutningsorka Fasi B | 149 150 151 152 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Raunútflutningsorka Fasi C | 153 154 155 156 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | Wh | Já |
Reactive Export Energy samtals | 157 158 159 160 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun |
Hvarfandi útflutningsorka A áfangi | 161 162 163 164 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Hvarfandi útflutningsorka Fasi B | 165 166 167 168 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Hvarfandi útflutningsorka Fasi C | 169 170 171 172 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VARh | Já |
Sýndarútflutningsorka samtals | 173 174 175 176 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Sýnileg útflutningsorka áfangi A | 177 178 179 180 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Sýnileg útflutningsorka áfangi B | 181 182 183 184 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Sýnileg útflutningsorka áfangi C | 185 186 187 188 |
R | U64 | 0 | 18.446e+18 | 0.00000001 | VAh | Já |
Meter Time Since Boot | 189 190 |
R | U32 | 0 | 4294967295 | 1 | Sekúndur | Nei |
Real-Time Clock Registers
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun | |
RTC - Stillt ár | 4000 | R/W | U16 | 2022 | 2060 | 1 | N/A | Nei | |
RTC - Stilltur mánuður | 4001 | R/W | U8 | 1 | 12 | 1 | N/A | Nei | |
RTC – Set Day of Month | 4002 | R/W | U8 | 1 | 31 | 1 | N/A | Nei | |
RTC – Stilltur vikudagur | 4003 | R/W | ENUM | 0 | 6 | 1 | N/A | Nei | |
RTC - Stilltu klukkustundir | 4004 | R/W | U8 | 0 | 23 | 1 | Kl | Nei | |
RTC - Stilltu mínútur | 4005 | R/W | U8 | 0 | 59 | 1 | mín | Nei | |
RTC - Stilltu sekúndur | 4006 | R/W | U8 | 0 | 23 | 1 | Sek | Nei | |
RTC - Skuldbinda tíma | 4007 | R/W | ENUM | 0 | 1 | 1 | N/A | Já | |
RTC - Núverandi ár | 4100 | R | U16 | 2022 | 2060 | 1 | N/A | Já | |
RTC - Núverandi mánuður | 4101 | R | U8 | 1 | 12 | 1 | N/A | Já | |
RTC - Núverandi dagur mánaðarins | 4102 | R | U8 | 1 | 31 | 1 | N/A | Já | |
RTC – Núverandi vikudagur | 0 = sunnudagur 6 = laugardagur |
4103 | R | ENUM | 0 | 6 | 1 | N/A | Já |
RTC - Núverandi klukkustundir | 4104 | R | U8 | 0 | 0 | 1 | Kl | Já | |
RTC – Núverandi fundargerðir | 4105 | R | U8 | 0 | 0 | 1 | mín | Já | |
RTC – Núverandi sekúndur | 4106 | R | U8 | 0 | 0 | 1 | Sek | Já | |
RTC – Núverandi AM/PM fáni, eða 0 | If in 24-hour mode, will return 0, if in 12-hour mode: 1 = AM, 2 = PM | 4107 | R | ENUM | 0 | 2 | 1 | N/A | Já |
Skráningarskrár
Log Source 1 through Log source 12 sets the source for the logging. Write the Modbus register 1-190 to the desired source to log that point. If a log source register has multiple registers all registers need to be set. For example, ef óskað er að heildartala raunverulegrar orku sé skráður þarf að stilla allar fjórar skrárnar.
To trigger a log event register 5000 (Logging – Trigger Source) needs to be set to the desired trigger mode, by default it is set to be disabled. Logging can be triggered with the timer, set on Modbus point 5001 (Logging – Trigger Interval) in seconds from 15-3600. Triggering can be set over COMMS by writing a ‘1’ to point 5015 (Logging – Trigger log creation), or Pulse In 1 or 2 can be set to trigger a log whenever a pulse is detected.
Lýsing | Reg. | R/W | Tegund | Min | Hámark | Mælikvarði | Einingar | Verslun | |
Skráning – Uppruni kveikja | 0 = Óvirk 1 = Tímamælir 2 = Samskipti 3 = Púls inn 1 4 = Púls í 2 |
5000 | R/W | ENUM | 0 | 4 | 1 | N/A | Já |
Skráning – Kveikjubil | 5001 | R/W | U16 | 15 | 3600 | 1 | Sek | Já | |
Skráning – Val á stillingu | 0 – “Continuous” – continue logging and overwrite old entries, sequentially 1 – “One Shot” – log until EEPROM is full, then stop logging and throw alarm |
5002 | R/W | ENUM | 0 | 1 | 1 | N/A | Já |
Skráning – Log Source 1 | 5003 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 2 | 5004 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 3 | 5005 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 4 | 5006 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 5 | 5007 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 6 | 5008 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 7 | 5009 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 8 | 5010 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 9 | 5011 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 10 | 5012 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 11 | 5013 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skráning – Log Source 12 | 5014 | R/W | U16 | 1 | 190 | 1 | N/A | Já | |
Skógarhögg – Kveiktu á því að búa til annál | 5015 | R/W | U16 | 0 | 1 | 1 | N/A | Já | |
Skógarhögg - Lestu skráningu á vísitölu | 5016 | R/W | U16 | 0 | 4096 | 1 | N/A | Já | |
Skógarhögg - Elsta vísitalan | 5100 | R | U16 | 0 | 4096 | 1 | N/A | Já | |
Skráning – Fjöldi skráninga | 5101 | R | U16 | 0 | 4096 | 1 | N/A | Já | |
Skógarhögg – Núverandi vísitala | 5102 | R | U16 | 0 | 4096 | 1 | N/A | Já | |
Skráning – Skráargögn 1 | 5103 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 2 | 5104 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 3 | 5105 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 4 | 5106 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 5 | 5107 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 6 | 5108 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 7 | 5109 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 8 | 5110 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 9 | 5111 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 10 | 5112 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 11 | 5113 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skráning – Skráargögn 12 | 5114 | R | U16 | 0 | 65535 | 1 | N/A | Já | |
Skógarhögg – Log tími stamp ári | 5115 | R | U16 | 0 | 256 | 1 | N/A | Já | |
Skógarhögg – Log tími stamp mánuði | 5116 | R | U16 | 0 | 12 | 1 | N/A | Já | |
Skógarhögg – Log tími stamp dag mánaðar | 5117 | R | U16 | 0 | 31 | 1 | N/A | Já | |
Skógarhögg – Log tími stamp klukkustundir | 5118 | R | U16 | 0 | 23 | 1 | N/A | Já | |
Skógarhögg – Log tími stamp mínútur | 5119 | R | U16 | 0 | 59 | 1 | N/A | Já | |
Skógarhögg – Log tími stamp sekúndur | 5120 | R | U16 | 0 | 59 | 1 | N/A | Já | |
Skógarhögg – CRC | 5121 | R | U16 | 0 | 65535 | 1 | N/A | Já |
Modbus aðgerðir
The EMX supports the following functions of the Modbus Application Protocol Specification, v1.1b3. Examplesum er ætlað að vera dæmigert; vísa til heildarforskriftarinnar fyrir spurningar eða skýringar.
Athugasemdir:
- The device address defaults to 247 (0xF7).
- Refer to the Modbus standard for CRC/LRC calculation procedures.
Gagnategundir
Natively, Modbus holding register functions only support the UINT16 type (2 bytes). The meter constructs additional types from two or more consecutive registers. Client interface software must support the same construction for proper communication:
# af skrám | Range (hexadecimal) | |
BOOL | 1 | 0 til 1 |
ENUM | 1 | 0 to specified upper limit |
UINT8 | 1 | 0 to 255 (0x00FF), unless otherwise noted |
UINT16 | 1 | 0 to 65535 (0xFFFF), unless otherwise noted |
INT16 | 1 | -32768 to -32767 (0xFFFF), unless otherwise noted |
UINT32 | 2 | 0 to 4294967295 (0xFFFFFFFF), unless otherwise noted |
UINT64 | 4 | 0 to 18.446e+18 (0xFFFFFFFFFFFFFFFF), unless otherwise noted |
INT64 | 4 | -9.233e+18 to 9.233e+18 (0xFFFFFFFFFFFFFFFF), unless otherwise noted |
UINT32, UINT64, and INT64 data always occupies two or four registers (4 and 8 bytes) in network byte order (MSB first). Read and write operations should address both registers.
Eftirfarandi frvamples show UINT32 encodings in a Modbus PDU beginning at byte [n], register [r]:
Gildi | Aukastafur | [n] | [n+1] | [n+2] | [n+3] |
0xAABBCCDD | 2864434397 | 0xAA | 0xBB | 0xCC | 0xDD |
0x01234567 | 19088743 | 0x12 | 0x34 | 0x56 | 0x78 |
0x00010000 | 65536 | 0x00 | 0x01 | 0x00 | 0x00 |
SKRÁÐIÐ | [r] | [r+1] |
0x03 Lestu eignarskrár
Skilar einum eða fleiri skrám í samliggjandi blokk:
Beiðni | Stærð | Skýringar |
[0] Device Address | 1 | Alltaf 0x03 ? = 0 to 65535 (0xFFFF) ? = 1 to 125 registers |
[1] Function Code | 1 | |
[2] Starting Address | 2 | |
[3] Register Count | 2 | |
[4] CRC | 2 |
Vel heppnuð lestur skilar innihaldi umbeðinna skráa:
Svar | Stærð | Skýringar |
[0] Device Address | 1 | Always 0x03 2 * ? |
[1] Function Code | 1 | |
[2] Byte Count | 1 | |
[3] Register Data | 2 * ? | |
[4] CRC | 2 |
Example 1: Read the line frequency of ΦA (020).
0x04 Lesa inntaksskrá
Les eina eða fleiri skrifvarða skrár í samliggjandi blokk:
Beiðni | Stærð | Skýringar |
[0] Device Address | 1 | Alltaf 0x04 ? = 0 to 65535 (0xFFFF) ? = 1 to 125 registers |
[1] Function Code | 1 | |
[2] Starting Address | 2 | |
[3] Register Count | 2 | |
[4] CRC | 2 |
Vel heppnuð lestur skilar innihaldi umbeðinna skráa:
Svar | Stærð | Skýringar |
[0] Device Address | 1 | Always 0x04 2 * ? |
[1] Function Code | 1 | |
[2] Byte Count | 1 | |
[3] Register Data | 2 * ? | |
[4] CRC | 2 |
Example 1: Read the line frequency of ΦA (020).
0x06 Skrifa staka skrá
Writes a value to a single register:
Beiðni | Stærð | Skýringar |
[0] Device Address | 1 | Alltaf 0x06 ? = 0 to 65535 (0xFFFF) ? = 0 to 65535 (0xFFFF) |
[1] Function Code | 1 | |
[2] Register Address | 2 | |
[3] Register Value | 2 | |
[4] CRC | 2 |
Successful writes echo the original request:
Svar | Stærð | |
[0] Device Address | 1 | Alltaf 0x06 ? ? |
[1] Function Code | 1 | |
[2] Register Address | 2 | |
[3] Register Value | 2 | |
[4] CRC | 2 |
Example 1: Change the phase configuration (2000).
0x10 Write Multiple Registers
Skrifar eitt eða fleiri skrár í samliggjandi blokk:
Beiðni | Stærð | Skýringar |
[0] Device Address | 1 | Alltaf 0x10 ? = 0 to 65535 (0xFFFF) ? = 1 to 123 registers Always 2 * ? ? … |
[1] Function Code | 1 | |
[2] Starting Address | 2 | |
[3] Write Count | 2 | |
[4] Byte Count | 1 | |
[5] Write Registers | 2 * ? | |
[6] CRC | 2 |
Successful writes echo the Starting Address and Write Count:
Beiðni | Stærð | Skýringar |
[0] Device Address | 1 | Alltaf 0x10 ? ? |
[1] Function Code | 1 | |
[2] Starting Address | 2 | |
[3] Write Count | 2 | |
[4] CRC | 2 |
Example 1: Change phase configuration (2000) and CT type (2001) in one write:
MODBUS undantekningarkóðar
When the Modbus interface encounters an error, it will return an exception code. The most common errors are described in the table below. Additional information about exception codes may be found in the reference document.
Tilvísun: https://modbus.org/docs/Modbus_Application_Protocol_V1_1b.pdf
MODBUS undantekningarkóðar | ||
Kóði | Nafn | Merking |
01 | ÓLÖGLEGT STARF | The function code received in the query is not an allowable action for the server (or slave). This may be because the function code is only applicable to newer devices and was not implemented in the unit selected. It could also indicate that the server (or slave) is in the wrong state to process a request of this type, for example vegna þess að það er óstillt og er beðið um að skila skráargildum. |
02 | ÓLÖGLEGT GAGNAHÉR | The data address received in the query is not an allowable address for the server (or slave). More specifically, the combination of reference number and transfer length is invalid. For a controller with 100 registers, the PDU addresses the first register as 0, and the last one as 99. If a request is submitted with a starting register address of 96 and a quantity of registers of 4, then this request will successfully operate (address-wise at least) on registers 96, 97, 98, 99. If a request is submitted with a starting register address of 96 and a quantity of registers of 5, then this request will fail with Exception Code 0x02 “Illegal Data Address” since it attempts to operate on registers 96, 97, 98, 99 and 100, and there is no register with address 100. |
03 | ÓLÖGLEGT GAGNAVERÐI | Gildi sem er í fyrirspurnargagnareitnum er ekki leyfilegt gildi fyrir netþjón (eða þræl). Þetta gefur til kynna galla í uppbyggingu afgangsins af flókinni beiðni, svo sem að ætluð lengd er röng. Það þýðir sérstaklega EKKI að gagnaatriði sem lagt er fram til geymslu í skrá hafi gildi sem er utan væntingar umsóknarforritsins, þar sem MODBUS siðareglur eru ekki meðvitaðir um mikilvægi einhvers tiltekins gildis einhvers tiltekins skráar. |
Gagnategundaviðskipti
The following sections provide information on how to convert from the standard U16 registers that Modbus provides into other formats. Some controllers or Modbus interfaces provide these conversions, in which case the user should utilize those methods, instead of the following conversions.
U16 to I16 Conversion
Conversion from a signed requires checking if the value is value returned (VALUE) is greater than the maximum for a 16-bit integer (32767), if the value is greater than the value 65536 must be subtracted off to calculate a negative value.
If VALUE > 32767
Then: VALUE = VALUE – 65536
Otherwise: VALUE = VALUE (do nothing)
Example:
Reading register 005 (Real power total) the device responds with 64536. This value is greater than 32767, which means it must be adjusted. By subtracting 65536 we get 64536 – 65536 = -1000, which is the correct value for the real power. Please note that in practice a scale value will need to be determined and applied to this output to get the value into watts or whatever units are applicable.
U16 to U32 Conversion
Conversion from two unsigned 16-bit registers into a 32-bit value can be done by reading the two necessary registers and multiplying the first (lower register address) register by 32678 and adding the second register.
VALUE = (REGISTER_LOW * 65536) + REGISTER_HIGH
Example:
Reading registers 035 and 036 which together are the system power on time. Register 035 has a value (REGISTER_LOW) of 6, register 036 (REGISTER_HIGH) has a value of 38784. Using the calculation we get (6 * 65536) + 38784 = 432000. This corresponds to the time in seconds that the device has been powered on. 5 Days = 5 * 24 * 60 * 60 = 432000 seconds.
U16 to U64 Conversion
Conversion from 4 unsigned 16-bit registers to a 64-bit register is necessary for using the energy accumulators on the EMX. This is done to maintain system accuracy over long operating durations, and to avoid conditions where the energies appear to cease updating. This follows a similar pattern as the U32 conversion. All four registers must be read, preferably simultaneously with a multi-register read operation. The lowest address register is REG_1, the highest is REG_4.
VALUE = REG_1 * 2^48 + REG_2 * 2^32 + REG_3 * 2^16 + REG_4 Or without the power notation
VALUE = REG_1 * 281,474,976,710,656 + REG_2 * 4,294,967,296 + REG_3 * 65536 + REG_4
Example:
Reading registers 093/094/095/096 which corresponds to the Real Import Energy Total (how much energy has been consumed by downstream devices). Register 093 (REG_1) reads 0, register 094 (REG_2) reads 13, register 095 (REG_3) reads 63559 and register 096 (REG_4) reads 22528.
The calculation is 0 * 281,474,976,710,656 + 13 * 4,294,967,296 + 63559 * 65536 + 22528 = 60000000000 when scaled down by the scale of 0.00000001 given in the table it’s 600.0 which is the number of Watt Hours of energy that the device has metered at that point.
U16 to I64 Conversion
All the net energy registers are signed values. A negative sign indicates that net power has been exported, a positive sign indicates that net power has been imported (consumed). To convert from four U16 registers to an I64 register first perform a conversion as described above. Next perform the following step:
If VALUE > (2^63)- 1
Then VALUE = VALUE – 2^64
Otherwise VALUE = VALUE (do nothing).
Appendix D: Hex and ASCII Conversions
HEX | DES | ASCII | 0x41 | 65 | A | 0x83 | 131 | ƒ | 0xC5 | 197 | Å |
0x00 | 0 | NULL | 0x42 | 66 | B | 0x84 | 132 | „ | 0xC6 | 198 | Æ |
0x01 | 1 | 0x43 | 67 | C | 0x85 | 133 | … | 0xC7 | 199 | Ç | |
0x02 | 2 | 0x44 | 68 | D | 0x86 | 134 | † | 0xC8 | 200 | È | |
0x03 | 3 | 0x45 | 69 | E | 0x87 | 135 | ‡ | 0xC9 | 201 | É | |
0x04 | 4 | 0x46 | 70 | F | 0x88 | 136 | ˆ | 0xCA | 202 | Ê | |
0x05 | 5 | 0x47 | 71 | G | 0x89 | 137 | ‰ | 0xCB | 203 | Ë | |
0x06 | 6 | 0x48 | 72 | H | 0x8A | 138 | Š | 0xCC | 204 | Ì | |
0x07 | 7 | 0x49 | 73 | I | 0x8B | 139 | ‹ | 0xCD | 205 | Í | |
0x08 | 8 | 0x4A | 74 | J | 0x8C | 140 | Œ | 0xCE | 206 | Î | |
0x09 | 9 | 0x4B | 75 | K | 0x8D | 141 | 0xCF | 207 | Ï | ||
0x0A | 10 | 0x4C | 76 | L | 0x8E | 142 | Ž | 0xD0 | 208 | Ð | |
0x0B | 11 | 0x4D | 77 | M | 0x8F | 143 | 0xD1 | 209 | Ñ | ||
0x0C | 12 | 0x4E | 78 | N | 0x90 | 144 | 0xD2 | 210 | Ò | ||
0x0D | 13 | 0x4F | 79 | O | 0x91 | 145 | ‘ | 0xD3 | 211 | Ó | |
0x0E | 14 | 0x50 | 80 | P | 0x92 | 146 | ’ | 0xD4 | 212 | Ô | |
0x0F | 15 | 0x51 | 81 | Q | 0x93 | 147 | “ | 0xD5 | 213 | Õ | |
0x10 | 16 | 0x52 | 82 | R | 0x94 | 148 | ” | 0xD6 | 214 | Ö | |
0x11 | 17 | 0x53 | 83 | S | 0x95 | 149 | • | 0xD7 | 215 | × | |
0x12 | 18 | 0x54 | 84 | T | 0x96 | 150 | – | 0xD8 | 216 | Ø | |
0x13 | 19 | 0x55 | 85 | U | 0x97 | 151 | — | 0xD9 | 217 | Ù | |
0x14 | 20 | 0x56 | 86 | V | 0x98 | 152 | ˜ | 0xDA | 218 | Ú | |
0x15 | 21 | 0x57 | 87 | W | 0x99 | 153 | ™ | 0xDB | 219 | Û | |
0x16 | 22 | 0x58 | 88 | X | 0x9A | 154 | š | 0xDC | 220 | Ü | |
0x17 | 23 | 0x59 | 89 | Y | 0x9B | 155 | › | 0xDD | 221 | Ý | |
0x18 | 24 | 0x5A | 90 | Z | 0x9C | 156 | œ | 0xDE | 222 | Þ | |
0x19 | 25 | 0x5B | 91 | [ | 0x9D | 157 | 0xDF | 223 | ß | ||
0x1A | 26 | 0x5C | 92 | \ | 0x9E | 158 | ž | 0xE0 | 224 | à | |
0x1B | 27 | 0x5D | 93 | ] | 0x9F | 159 | Ÿ | 0xE1 | 225 | á | |
0x1C | 28 | 0x5E | 94 | ^ | 0xA0 | 160 | 0xE2 | 226 | â | ||
0x1D | 29 | 0x5F | 95 | _ | 0xA1 | 161 | ¡ | 0xE3 | 227 | ã | |
0x1E | 30 | 0x60 | 96 | ` | 0xA2 | 162 | ¢ | 0xE4 | 228 | ä | |
0x1F | 31 | 0x61 | 97 | a | 0xA3 | 163 | £ | 0xE5 | 229 | å | |
0x20 | 32 | 0x62 | 98 | b | 0xA4 | 164 | ¤ | 0xE6 | 230 | æ | |
0x21 | 33 | ! | 0x63 | 99 | c | 0xA5 | 165 | ¥ | 0xE7 | 231 | ç |
0x22 | 34 | “ | 0x64 | 100 | d | 0xA6 | 166 | ¦ | 0xE8 | 232 | è |
0x23 | 35 | # | 0x65 | 101 | e | 0xA7 | 167 | § | 0xE9 | 233 | é |
0x24 | 36 | $ | 0x66 | 102 | f | 0xA8 | 168 | ¨ | 0xEA | 234 | ê |
0x25 | 37 | % | 0x67 | 103 | g | 0xA9 | 169 | © | 0xEB | 235 | ë |
0x26 | 38 | & | 0x68 | 104 | h | 0xAA | 170 | ª | 0xEC | 236 | ì |
0x27 | 39 | ‘ | 0x69 | 105 | i | 0xAB | 171 | « | 0xED | 237 | í |
0x28 | 40 | ( | 0x6A | 106 | j | 0x AC | 172 | ¬ | 0xEE | 238 | î |
0x29 | 41 | ) | 0x6B | 107 | k | 0xAD | 173 | – | 0xEF | 239 | ï |
0x2A | 42 | * | 0x6C | 108 | l | 0xAE | 174 | ® | 0xF0 | 240 | ð |
0x2B | 43 | + | 0x6D | 109 | m | 0xAF | 175 | ¯ | 0xF1 | 241 | ñ |
0x2C | 44 | , | 0x6E | 110 | n | 0xB0 | 176 | ° | 0xF2 | 242 | ò |
0x2D | 45 | – | 0x6F | 111 | o | 0xB1 | 177 | ± | 0xF3 | 243 | ó |
0x2E | 46 | . | 0x70 | 112 | p | 0xB2 | 178 | ² | 0xF4 | 244 | ô |
0x2F | 47 | / | 0x71 | 113 | q | 0xB3 | 179 | ³ | 0xF5 | 245 | õ |
0x30 | 48 | 0 | 0x72 | 114 | r | 0xB4 | 180 | ´ | 0xF6 | 246 | ö |
0x31 | 49 | 1 | 0x73 | 115 | s | 0xB5 | 181 | µ | 0xF7 | 247 | ÷ |
0x32 | 50 | 2 | 0x74 | 116 | t | 0xB6 | 182 | ¶ | 0xF8 | 248 | ø |
0x33 | 51 | 3 | 0x75 | 117 | u | 0xB7 | 183 | · | 0xF9 | 249 | ù |
0x34 | 52 | 4 | 0x76 | 118 | v | 0xB8 | 184 | ¸ | 0xFA | 250 | ú |
0x35 | 53 | 5 | 0x77 | 119 | w | 0xB9 | 185 | ¹ | 0xFB | 251 | û |
0x36 | 54 | 6 | 0x78 | 120 | x | 0xBA | 186 | º | 0xFC | 252 | ü |
0x37 | 55 | 7 | 0x79 | 121 | y | 0xBB | 187 | » | 0xFD | 253 | ý |
0x38 | 56 | 8 | 0x7A | 122 | z | 0xBC | 188 | ¼ | 0xFE | 254 | þ |
0x39 | 57 | 9 | 0x7B | 123 | { | 0xBD | 189 | ½ | 0xFF | 255 | ÿ |
0x3A | 58 | : | 0x7C | 124 | | | 0xBE | 190 | ¾ | |||
0x3B | 59 | ; | 0x7D | 125 | } | 0xBF | 191 | ¿ | |||
0x3C | 60 | < | 0x7E | 126 | ~ | HEX | DES | LATIN-1 | |||
0x3D | 61 | = | 0x7F | 127 | 0xC0 | 192 | À | ||||
0x3E | 62 | > | HEX | DES | LATIN-1 | 0xC1 | 193 | Á | |||
0x3F | 63 | ? | 0x80 | 128 | € | 0xC2 | 194 | Â | |||
HEX | DES | ASCII | 0x81 | 129 | 0xC3 | 195 | Ã | ||||
0x40 | 64 | @ | 0x82 | ‚130 | 0xC4 | 196 | Ä |
EMX-IP Modbus Protocol Guide
Síða 22 af 23
154-0050-0A
Skjöl / auðlindir
![]() |
SENVA EMX-IP User Interface and Modbus [pdfNotendahandbók 154-0050-0A, EMX-IP User Interface and Modbus, EMX-IP, User Interface and Modbus, Modbus |